H261--FY24: Load Bank Testing UPS System Maintenance Base+4

Agency: VETERANS AFFAIRS, DEPARTMENT OF
Level of Government: Federal
Category:
  • H - Quality Control, Testing, and Inspection Services
Opps ID: NBD00159516752827280
Posted Date: Mar 26, 2024
Due Date: Apr 4, 2024
Solicitation No: 36C24824Q0663
Source: https://sam.gov/opp/f47ec90a8d...
Follow
H261--FY24: Load Bank Testing UPS System Maintenance Base+4
Active
Contract Opportunity
Notice ID
36C24824Q0663
Related Notice
Department/Ind. Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-tier
VETERANS AFFAIRS, DEPARTMENT OF
Office
248-NETWORK CONTRACT OFFICE 8 (36C248)
Looking for contract opportunity help?

APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.

APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.

The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).

General Information View Changes
  • Contract Opportunity Type: Combined Synopsis/Solicitation (Updated)
  • All Dates/Times are: (UTC-04:00) EASTERN STANDARD TIME, NEW YORK, USA
  • Updated Published Date: Mar 26, 2024 04:16 pm EDT
  • Original Published Date: Mar 18, 2024 06:07 pm EDT
  • Updated Date Offers Due: Apr 04, 2024 04:30 pm EDT
  • Original Date Offers Due: Apr 04, 2024 04:30 pm EDT
  • Inactive Policy: Manual
  • Updated Inactive Date: Jul 03, 2024
  • Original Inactive Date: Jul 03, 2024
  • Initiative:
    • None
Classification
  • Original Set Aside: Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14)
  • Product Service Code: H261 - EQUIPMENT AND MATERIALS TESTING- ELECTRIC WIRE AND POWER DISTRIBUTION EQUIPMENT
  • NAICS Code:
    • 811210 - Electronic and Precision Equipment Repair and Maintenance
  • Place of Performance:
    Malcolm Randall VAMC 1601 SW Archer Rd Gainesville , FL 32608
    USA
Description View Changes
This amendment to RFQ 36C24824Q0663 is to answer additional questions submitted.
1. Does this mean the VA will accept a battery test & report via a midtronics or similar device instead of the load bank test for both units?

Answer: If the load bank testing is still required, can you confirm the below. The MBP needs to be external to the UPS for there to be no disruption/loss of load.

2. The Riello UPS does have an external MBP, so a load bank test is needed?
Answer: Correct

3. The Mitsu UPS does not have an external MBP, so a load bank test is not needed?
Answer: Battery testing acceptable.
Attachments/Links
Contact Information
Contracting Office Address
  • 8875 HIDDEN RIVER PARKWAY
  • TAMPA , FL 33637
  • USA
Primary Point of Contact
Secondary Point of Contact


History

TRY FOR FREE

Not a USAOPPS Member Yet?

Get unlimited access to thousands of active local, state and federal government bids and awards in All 50 States.

Start Free Trial Today >