Mobile Generator 2 Mega Watt; 1050 Gal double wall fuel tank each gen set 80 Gal DEF tank Exterior fuel & DEF supply connections, ABS, Air Ride, Two Axle, 48- ISO container chassis
Agency: | VETERANS AFFAIRS, DEPARTMENT OF |
---|---|
Level of Government: | Federal |
Category: |
|
Opps ID: | NBD00159738918906637 |
Posted Date: | May 17, 2023 |
Due Date: | Jun 4, 2023 |
Solicitation No: | 23-AP-4217-GEN |
Source: | https://sam.gov/opp/c8b189970d... |
Procurement Technical Assistance Centers (PTACs) are an official government contracting resource for small businesses. Find your local PTAC (opens in new window) for free government expertise related to contract opportunities.
- Contract Opportunity Type: Sources Sought (Original)
- All Dates/Times are: (UTC-04:00) EASTERN STANDARD TIME, NEW YORK, USA
- Original Published Date: May 17, 2023 04:09 pm EDT
- Original Response Date: Jun 04, 2023 04:00 pm EDT
- Inactive Policy: 15 days after response date
- Original Inactive Date:
-
Initiative:
- None
- Original Set Aside:
- Product Service Code:
-
NAICS Code:
- 333618 - Other Engine Equipment Manufacturing
-
Place of Performance:
Daytona Beach , FL 32117USA
2 Mega Watts Mobile Generator (Brand Name or Equal)
ENGINE PACKAGE DESCRIPTION
Clean Emissions Module
(CEM) w/integrated Diesel Oxidation Catalyst(DOC),
Selective Catalytic Reduction (SCR), & Ammonia Oxidation Catalyst
(AMOX) AND IS EPA TIER 4F EMISSIONS CERTIFIED.
CIRCUIT BREAKERS
3200A electrically operated, fixed type, 3 pole, insulated case circui
Basler UMR
Solid state trip unit for overload (time overcurrent) and fault
(instantaneous) overcurrent protection
Includes DC shunt trip coil activated on any monitored engine or
electrical fault
Undervoltage release
COOLING SYSTEM
Minimum 43 Deg C (117 Deg F) 500 M (1640 ft.)
Vertically mounted radiator with vertical discharge
Variable Speed Fan and belt guards
Coolant drain line with internal valve
Coolant sight gauge, level switch with shutdown
Extended Life Coolant (50/50)
Jacket water heater with isolation valves
DISTRIBUTION PANEL
Busbar connections
Externally-accessible, Vibration Isolated, 3200A Frame, 100 Ka, IC,
3-pole electrically operated breaker with lock out tag out provision.
Dedicated power cubicle in container wall.
Dedicated cable tie down points to secure load cables and relieve
cable stress.
Hinged load cover door which must be closed for main breaker operation
Neutral earth link
Shunt Trip
Remote start terminals
Lockable door
Side hinged Lockable doors with rust resistant
pinned hinges.
Bus bar connection with easy access for connections
through bottom of unit, even when on the ground.
Separate control and load sections.
Shore Power Circuits for
240V 30A Generator heater, Fuel Transferer pump &
Remote DEF tank heater
240V 50A Air Compressor Heater, Jacket Water Heater,
DEF Tank Heater
120V Battery Charger
Paralleling interface connections
Remote start terminals
Current transformers, hard mounted.
ENCLOSURES
48' ISO High Cube container
Sound attenuated to 82.7 dB(A) at 7 meters at 75% Prime
Spill containment - (110% onboard engine fluids)
Five Cat Key lockable (or padlockable) personnel doors with
hold open rods
Package mounted bus bar connections
Vertical air discharge
Removable six step stairway with handrail
Stairways (3) and handrails (3) packaged in radiator compartment
(8) - 24VDC Interior Lights with 60 minute wall mounted timer
(1) - 120VAC wall mounted duplex GFI receptacle(connected to shore power and generator power)
Sound attenuated intake
EXHAUST SYSTEM
Integral with flexible connector
FUEL SYSTEM
1050 Gallon double wall fuel tank for each generator set
80 Gallon DEF tank
Exterior fuel & DEF supply connections
Dual Racor Filters with water separator and vacuum gauge
Fuel Filter Spill Containment with drain
Radiator mounted fuel cooler
Motorized fuel priming pump
Digital fuel level gauge
UL142 & UN31A Approved
GENERATORS AND GENERATOR ATTACHMENTS
3 Phase brushless, 6 lead, Permanent Magnet Excited
Class H insulation, Class F temperature rise at 40DEC
ambient (105C prime)
Anti-condensation space heaters
Includes Integrated voltage regulator (IVR) with
KVAR/PF modes, RFI suppression, min/max exciter limiter
and exciter diode monitor.
VOLTAGE REGULATION
Integrated voltage regulator,
microprocessor based.
Manual raise/lower voltage adjust capability
RFI suppression, exciter limiter and exciter diode monitoring
STARTING/CHARGING SYSTEM
60 amp charging alternator
24 Volt Electric Starting Motors
Two Batteries (24V-Maintenance Free, 1400 CCA)
Battery rack w/cables mounted in diamond plate cover
Battery disconnect switch
50 Amp battery charger (wall mounted)
Solar power battery maintainer with isolator
CONTROL SYSTEM
Generator mounted EMCP 4.4 provides power metering, protective
relaying and engine and generator control, monitoring and paralleling
NEMA 12, IP44 Dust Proof Enclosure
UL508A Listed
Integration with the IVR provides enhanced system monitoring.
Ability to view and reset diagnostics of all controls networked on
primary CAN datalink eliminates need for separate service tools
for troubleshooting.
True RMS AC metering, 3 phase
Emergency Stop Button
Panel illuminating lights
Display navigation keys including 2 shortcut keys for engine
and generator parameters
Fuel level monitoring and control
Rated/Idle Speed Switch
Multiple stored setpoint group selection via switched input
Controls:
Run/Auto/Stop
Engine cool-down timer
Engine cycle crank
Voltage & Speed Adjustments
Panel illuminating lights
Alarm acknowledge
Alarm reset
Digital indication for:
RPM
Operating hour
Oil pressure (psi, kPa or bar)
Coolant temperature (OEC or OEF)
DC Volts
Oil Temperature (OEC or OEF)
L-L Volts, L-N Volts, Phase amps
Average volts, Amps, Frequency
ekW, kVa, kVAR, kW-hr, % kW,
Power Factor (Average, Phase)
kW-hr, kVA-hr (total)
Warning/Shutdown with indicating lights for:
Low oil pressure
High coolant temperature
Overspeed
Emergency stop
Failure to start (overcrank)
Low coolant level
High oil temperature
Programmable Protective Relaying Functions
Phase over/under Voltage
Under and Over Frequency
Reverse Power
Current Balance
Over Current (Phase and Total)
Loss of Excitation
Bus Phase Sequence
Modes of operation
Single Unit Island Mode
Multiple Unit Island Mode - Automatic and Manual Paralleling
Single Unit Utility Parallel Mode - Automatic and Manual Paralleling
Paralleling Functions
Load sharing
Load sense/Load demand
Load Shed/Load add
Dead bus arbitration
Synchronizing
TRAILER
Anti-lock Brake System
Air Ride
Two Axle, 48- ISO container chassis
- 8875 HIDDEN RIVER PARKWAY
- TAMPA , FL 33637
- USA
- Darrin Alexander
- darrin.alexander2@va.gov
- Phone Number (407) 646-4003
- May 17, 2023 04:09 pm EDTSources Sought (Original)